Description
405TSTGS6503 – Marathon 100 HP Explosion Proof Motor, 3 phase, 3600 RPM, 230/460 V, 405TS Frame, EPFC – E578
405TSTGS6503 Marathon Explosion Proof NEMA Motors
Please advise CFM, static pressure, voltage, phase, and/or horsepower on specifications, drawings, or existing equipment for an accurate quote.
General Specifications
UPC: | 722856023957 | Weight: | 0 LB |
Packaged Length: | 44.88 IN | Packaged Width: | 39.25 IN |
Packaged Height: | 28.62 IN |
Nameplate Specifications
Output HP: | 100 Hp | Output KW: | 75.0 kW |
Frequency: | 60 Hz | Voltage: | 230/460 V |
Current: | 216.0/108.0 A | Speed: | 3565 rpm |
Service Factor: | 1.15 | Phase: | 3 |
Efficiency: | 94.5 % | Power Factor: | 91.5 |
Duty: | Continuous | Insulation Class: | F |
Design Code: | B | KVA Code: | G |
Frame: | 405TS | Enclosure: | Explosion Proof Fan cooled |
Thermal Protection: | Thermostats (N/C) | Ambient Temperature: | 40 °C |
Drive End Bearing Size: | 6313 | Opp Drive End Bearing Size: | 6313 |
UL: | UL Listed And CSA Certified | CSA: | Y |
CE: | N | IP Code: | 54 |
Hazardous Location: | EXP PROOF CL I GR C&D CL II GR F&G T3B |
Technical Specifications
Electrical Type: | Squirrel Cage Inverter Rated | Starting Method: | Line Or Inverter |
Poles: | 2 | Rotation: | Reversible |
Resistance Main: | .051 Ohms | Mounting: | Rigid base |
Motor Orientation: | Horizontal | Drive End Bearing: | Ball |
Opp Drive End Bearing: | Ball | Frame Material: | Cast Iron |
Shaft Type: | TS | Overall Length: | 34.12 in |
Frame Length: | 16.75 in | Shaft Diameter: | 2.125 in |
Shaft Extension: | 4.5 in | Assembly/Box Mounting: | F1 ONLY |
Speed Characteristics
Curvepoint | Current (Amps) | Current (%) | Torque (ft-lbs) | (%) | Speed (RPM) | Rated Output (KW) | Power Factor (%) | Rated Output (Hp) |
1/3 | 675.00 | 625.0 | 200.00 | 136.0 | 1,200 | 100.00 | ||
Locked-Rotor | 725.00 | 671.0 | 230.00 | 156.0 | 0 | 31.0 | 100.00 | |
Break-Down | 425.00 | 394.0 | 410.00 | 279.0 | 3,415 | 67.0 | 100.00 | |
2/3 | 600.00 | 556.0 | 240.00 | 163.0 | 2,400 | 100.00 | ||
Pull-Up | 650.00 | 602.0 | 200.00 | 136.0 | 1,800 | 100.00 | ||
No Load | 24.00 | 22.0 | 0.00 | 0.0 | 3,600 | 100.00 | ||
Full Load | 108.00 | 100.0 | 147.00 | 100.0 | 3,565 | 100.00 |
Load Characteristics
% of Rated Load | 0 % | 25 % | 50 % | 75 % | 100 % | 115 % | 125 % |
Current (Amps) | 24.00 | 36.00 | 57.50 | 81.50 | 108.00 | 124.00 | 135.00 |
Rated Output (KW) | 2.50 | 21.00 | 40.00 | 59.50 | 79.00 | 91.00 | 99.00 |
Efficiency (%) | 0.0 | 90.2 | 94.1 | 94.5 | 94.5 | 94.5 | 94.5 |
Power Factor (%) | 7.5 | 71.0 | 86.0 | 90.5 | 91.5 | 91.5 | 91.5 |
Speed (RPM) | 3,600 | 3,592 | 3,582 | 3,572 | 3,565 | 3,560 | 3,555 |
Temp. Rise @ FL | 0.0 | 0.0 | 0.0 | 0.0 | 65.0 | 85.0 | 110.0 |
Torque (ft-lbs) | 0.00 | 36.50 | 73.50 | 110.00 | 147.00 | 170.00 | 185.00 |